Language
Shopping Cart

MT-NET-BD3 Controllore 8 DIN 42 I/O

SKU
MT-NET-BD3*02
Get a Quote
MultiNet programmable controller with 42 I/O display, Ethernet, 2 Modbus (RS485)
ANALOGUE INPUTS
Configurable in pairs

DIGITAL INPUTS
2 optoisolated digital inputs (Pulse count + Frequency reading)
Note: it measures a signal with a maximum frequency of 2kHz.
The digital inputs can be used as pulse counters. The duration of the pulse (positive or negative) must be greater than 0.15ms.

10 normal optoisolated digital inputs
Working voltage + 24Vac / dc. Current consumption max. 5mA
The digital inputs can be used as pulse counters. The pulse length (both positive and negative) must be greater than 20ms (if DI3, DI4) or 40ms (if DI5, DI6, DI7, DI8, DI13)

ANALOGUE OUTPUTS
4 outputs (voltage modulation 0..10V),
• Range: 0..1000,
• Accuracy: 1% fs,
• Resolution: 1 digit,
• Load impedance:> 700Ω.

2 configurable outputs:
• 4.20mA current modulation;
• ON-OFF current: the current (ON) is 25mA, the current (OFF) is 0mA. .. (They can drive DGSRMVs);
• Voltage modulation 0..10V,
Range: 0..1000, Accuracy: 1% fs,
Resolution: 1 digit, load impedance:> 700Ω;
• PWM mode: frequency from 1Hz to 2000Hz (1Hz accuracy), Duty Cycle from 0.0% to 100.0% (accuracy 0.1%), Open Collector output, 30mA, + 24Vdc max.

DIGITAL OUTPUTS
10 relays 3 A SPST + 250Vac 2 relays from 1 A SPDT + 250Vac
More Information
Power supply 24 V AC, 24 V DC
Power consumption Max. [VA] 25
Power consumption [W] 14
Analog outputs 6
Digital outputs 12
Analog inputs 12
Digital inputs 12
Controller type Programmable
IP 20
Communication protocol CANopen, Modbus RTU/ASCII, Modbus TCP/IP
Display LCD monocromatico 128x64 px, retroilluminato a LED, con 4 LED di stato